Wire Gauge Calculator
Find an estimated wire size in AWG from amps or watts. Check voltage drop, convert AWG to mm², and compare common wire sizes for electrical runs.
Calculate wire size
Amps Alone Do Not Set Wire Size
A useful wire-size estimate also depends on voltage, one-way length, conductor material, and allowable voltage drop. For US residential work, ampacity and installation conditions must also be checked. This page’s default example — 20 A, 120 V, 50 ft, 3%, copper — recommends 10 AWG (2.42 V / 2.02% drop). Ampacity still lists 12 AWG for 20 A. Change the inputs above for a more specific estimate.
Browser-only estimate. Circuit inputs are not uploaded to EverydayTools.
Advertisement
What Is a Wire Gauge Calculator?
A wire gauge calculator estimates a conductor size in AWG from electrical load and run conditions. This page can start from amps or watts, then check voltage drop over a one-way length and compare that size with a copper NM-B 60 °C ampacity reference when the current fits the shipped table. It is a planning estimate, not a substitute for the voltage drop calculator, a breaker sizing calculator, or a licensed design.
What Is AWG?
American Wire Gauge (AWG) is a standardized size system. A larger AWG number is a thinner wire. 12 AWG is thicker than 14 AWG. Sizes thicker than 1 AWG use 1/0, 2/0, 3/0, and 4/0 (also written 0, 00, 000, 0000).
How to Use the Wire Gauge Calculator
- Enter load amps, or watts plus voltage.
- Choose DC, AC single-phase, or AC three-phase.
- Set one-way length in feet or meters and an allowable voltage drop.
- Select copper or aluminum and read the recommended AWG, drop, and assumptions.
In AWG converter mode, pick a size to see diameter, mm², and kcmil. After you have a candidate gauge, confirm the actual run with the voltage drop calculator and match protection with the breaker sizing calculator.
How Wire Size Is Calculated
Voltage-drop area uses A = (k × ρ × L × I) / Vdrop, where k is 2 for DC and single-phase or √3 for balanced three-phase, L is one-way length, and ρ is resistivity at the selected temperature. The next larger stocked AWG whose area meets that result is the voltage-drop minimum. Copper ampacity, when shown, comes from the shipped 60 °C NM-B table. The recommended size is the thicker of those two checks.
AWG diameter is d(mm) = 0.127 × 92((36 − n) / 39), with 0 = 1/0, −1 = 2/0, −2 = 3/0, −3 = 4/0. Area is πd²/4. Watts become current as I = P / V (DC or unity-PF single-phase) or I = P / (√3 × V × PF) for three-phase. Power factor and efficiency stay visible in Advanced options.
Wire Gauge vs Wire Size
People search “wire gauge” and “wire size” for the same job: pick a conductor. Gauge usually means the AWG number. Size can also mean mm² or the insulated cable’s outside diameter. This calculator sizes the metal conductor, not the jacket.
AWG to mm and mm² Conversion
12 AWG is 2.053 mm in diameter and 3.309 mm². 10 AWG is 2.588 mm and 5.261 mm². Use the converter for any size from 4/0 through 40. mm is diameter; mm² is cross-sectional area.
AWG Wire Gauge Chart
Diameters and areas use the AWG formula above. Resistance is copper at 75 °C in ohms per 1,000 ft — Table 8 values where that table includes the size, otherwise calculated from area.
| AWG | Diameter (mm) | Diameter (in) | Area (mm²) | Resistance (Ω/kft) |
|---|---|---|---|---|
| 4/0 | 11.684 | 0.4600 | 107.22 | 0.061 |
| 3/0 | 10.405 | 0.4096 | 85.03 | 0.077 |
| 2/0 | 9.266 | 0.3648 | 67.43 | 0.097 |
| 1/0 | 8.251 | 0.3249 | 53.48 | 0.122 |
| 1 | 7.348 | 0.2893 | 42.41 | 0.154 |
| 2 | 6.544 | 0.2576 | 33.63 | 0.194 |
| 3 | 5.827 | 0.2294 | 26.67 | 0.245 |
| 4 | 5.189 | 0.2043 | 21.15 | 0.308 |
| 5 | 4.621 | 0.1819 | 16.77 | 0.381 |
| 6 | 4.115 | 0.1620 | 13.30 | 0.491 |
| 7 | 3.665 | 0.1443 | 10.55 | 0.606 |
| 8 | 3.264 | 0.1285 | 8.366 | 0.764 |
| 9 | 2.906 | 0.1144 | 6.634 | 0.963 |
| 10 | 2.588 | 0.1019 | 5.261 | 1.210 |
| 11 | 2.305 | 0.0907 | 4.172 | 1.532 |
| 12 | 2.053 | 0.0808 | 3.309 | 1.930 |
| 13 | 1.828 | 0.0720 | 2.624 | 2.435 |
| 14 | 1.628 | 0.0641 | 2.081 | 3.070 |
| 15 | 1.450 | 0.0571 | 1.650 | 3.872 |
| 16 | 1.291 | 0.0508 | 1.309 | 4.890 |
| 17 | 1.150 | 0.0453 | 1.038 | 6.157 |
| 18 | 1.024 | 0.0403 | 0.8230 | 7.770 |
| 19 | 0.912 | 0.0359 | 0.6527 | 9.791 |
| 20 | 0.812 | 0.0320 | 0.5176 | 12.346 |
| 21 | 0.723 | 0.0285 | 0.4105 | 15.568 |
| 22 | 0.644 | 0.0253 | 0.3255 | 19.630 |
| 23 | 0.573 | 0.0226 | 0.2582 | 24.753 |
| 24 | 0.511 | 0.0201 | 0.2047 | 31.214 |
| 25 | 0.455 | 0.0179 | 0.1624 | 39.360 |
| 26 | 0.405 | 0.0159 | 0.1288 | 49.631 |
| 27 | 0.361 | 0.0142 | 0.1021 | 62.584 |
| 28 | 0.321 | 0.0126 | 0.0810 | 78.917 |
| 29 | 0.286 | 0.0113 | 0.0642 | 99.513 |
| 30 | 0.255 | 0.0100 | 0.0509 | 125.483 |
| 31 | 0.227 | 0.0089 | 0.0404 | 158.231 |
| 32 | 0.202 | 0.0080 | 0.0320 | 199.526 |
| 33 | 0.180 | 0.0071 | 0.0254 | 251.598 |
| 34 | 0.160 | 0.0063 | 0.0201 | 317.259 |
| 35 | 0.143 | 0.0056 | 0.0160 | 400.056 |
| 36 | 0.127 | 0.0050 | 0.0127 | 504.461 |
| 37 | 0.113 | 0.0045 | 0.0100 | 636.114 |
| 38 | 0.101 | 0.0040 | 0.0080 | 802.125 |
| 39 | 0.090 | 0.0035 | 0.0063 | 1,011.461 |
| 40 | 0.080 | 0.0031 | 0.0050 | 1,275.428 |
What Size Wire for Common Amp Loads?
These answers use this page’s default copper, 120 V, AC single-phase, 50 ft one-way, 3% drop, 75 °C resistivity, and the copper NM-B 60 °C ampacity table. Change length or voltage and the gauge can change. A short 20 A branch (12 AWG below) is not the same as a 50 ft 20 A run.
| Load | Recommended | Voltage-drop min | Ampacity reference |
|---|---|---|---|
| 20 A | 10 AWG | 10 AWG | 12 AWG |
| 30 A | 8 AWG | 8 AWG | 10 AWG |
| 40 A | 8 AWG | 8 AWG | 8 AWG |
| 50 A | 6 AWG | 6 AWG | 6 AWG |
| 60 A | 4 AWG | 6 AWG | 4 AWG |
| 100 A | 1 AWG | 4 AWG | 1 AWG |
What Size Wire for 20 Amps?
Copper NM-B at 60 °C lists 12 AWG for 20 A. On a 10 ft 120 V run this calculator therefore recommends 12 AWG. The default 50 ft example recommends 10 AWG because voltage drop needs more area than 12 AWG.
What Size Wire for 30 Amps?
Ampacity reference is 10 AWG (30 A). At 50 ft / 120 V / 3% the voltage-drop check moves the recommendation to 8 AWG.
What Size Wire for 40 Amps?
Both checks land on 8 AWG under the default 50 ft assumption. 8 AWG copper is listed at 40 A in the 60 °C table.
What Size Wire for 50 Amps?
Default-assumption result: 6 AWG. The 60 °C copper table lists 6 AWG at 55 A — still an estimate, not a universal 50 A cable rule.
What Size Wire for 60 Amps?
Ampacity moves the default-assumption result to 4 AWG (4 AWG is 70 A in the shipped table; 6 AWG is 55 A).
What Size Wire for 100 Amps?
Default-assumption result: 1 AWG. 1 AWG copper is listed at 110 A. Feeder methods, aluminum, and termination temperature often change this — use the related breaker and voltage drop tools and local rules.
Worked Wire-Size Examples
1,920 W at 120 V
Input: 16.00 A at 120 V, 50 ft one-way, copper, 3% target. Required area 2.840 mm² → voltage-drop minimum 12 AWG. Ampacity reference 12 AWG. Result: 12 AWG (Voltage drop and ampacity (same size)), about 3.09 V (2.57%).
15 A load
Input: 15.00 A at 120 V, 50 ft one-way, copper, 3% target. Required area 2.663 mm² → voltage-drop minimum 12 AWG. Ampacity reference 14 AWG. Result: 12 AWG (Voltage drop), about 2.90 V (2.41%).
12 V DC run
Input: 15.00 A at 12 V, 10 ft one-way, copper, 3% target. Required area 5.325 mm² → voltage-drop minimum 8 AWG. Ampacity reference 14 AWG. Result: 8 AWG (Voltage drop), about 0.23 V (1.91%).
Long 240 V run
Input: 20.00 A at 240 V, 200 ft one-way, copper, 3% target. Required area 7.100 mm² → voltage-drop minimum 8 AWG. Ampacity reference 12 AWG. Result: 8 AWG (Voltage drop), about 6.11 V (2.55%).
Copper vs aluminum
Input: 20.00 A at 120 V, 50 ft one-way, aluminum, 3% target. Required area 5.846 mm² → voltage-drop minimum 8 AWG. Ampacity reference not in the copper table. Result: 8 AWG (Voltage drop), about 2.52 V (2.10%).
How Wire Length Affects Voltage Drop
Drop scales with one-way length. Double the run and the required area roughly doubles for the same percent target. That is why 20 A at 10 ft can stay on 12 AWG while 20 A at 50 ft moves to 10 AWG on this page.
12V and 24V Wire Sizing
Percent drop is volts lost divided by system voltage. The same ohms and amps that are fine on 120 V look severe on 12 V or 24 V. A 15 A, 10 ft, 3% 12 V DC example on this page recommends 8 AWG. Use the 12 V / 24 V chips, then confirm the run in the voltage drop calculator.
Copper vs Aluminum Wire
Aluminum has higher resistivity, so the voltage-drop size is larger. The default 20 A / 50 ft copper example is 10 AWG; the same inputs in aluminum recommend 8 AWG. This tool does not invent an aluminum ampacity table — confirm current-carrying capacity for the actual cable type.
Common Wire Gauge Sizing Mistakes
- Choosing a gauge from amps alone and ignoring length.
- Ignoring voltage drop on long or low-voltage runs.
- Treating AWG and mm² as the same number.
- Confusing conductor diameter with the insulated cable’s outside diameter.
- Using a copper size for aluminum, or the reverse.
- Mixing 60 °C, 75 °C, and 90 °C ampacity columns.
- Assuming one ampacity table covers NM-B, THHN, UF, and every installation method.
- Skipping the 125% continuous-load check on heaters and similar loads.
- Treating an online estimate as NEC compliance or a permit.
When to Use This Calculator
Use it to interpret a step-count-style question — “what gauge do I need?” — from a known load, voltage, and one-way distance. Add branch loads first with the circuit load calculator, then size the breaker. For operating cost, use the electricity cost calculator.
Frequently Asked Questions
What is a wire gauge calculator?
It estimates an AWG conductor from load current or watts, voltage, one-way length, material, and an allowable voltage drop, then compares that size with a copper ampacity reference when one is available.
What size wire do I need for my amps?
Current is only one input. Voltage, length, material, and allowable drop can force a thicker wire than the ampacity pairing. Enter those values above instead of using a single amp-to-gauge chart.
What size wire for 20 amps?
Copper NM-B at 60 °C lists 12 AWG for 20 A, and a 10 ft 120 V example on this page stays on 12 AWG. The default 50 ft, 3% copper example recommends 10 AWG because voltage drop needs about 3.55 mm².
What size wire for 30 amps?
The shipped copper table lists 10 AWG at 30 A. Under this page’s default 50 ft / 120 V / 3% copper assumption the voltage-drop check recommends 8 AWG.
What size wire for 40 amps?
Under the same 50 ft / 120 V / 3% copper assumption both checks land on 8 AWG. 8 AWG copper is listed at 40 A in the 60 °C table.
What size wire for 50 amps?
The default-assumption result is 6 AWG. The 60 °C copper table lists 6 AWG at 55 A. Longer runs or aluminum can require a larger conductor.
What size wire for 60 amps?
Default-assumption result is 4 AWG, because 6 AWG is listed at 55 A and 4 AWG at 70 A in the shipped copper table. Voltage drop on a 50 ft 120 V run would have allowed 6 AWG.
Does wire length affect wire size?
Yes. Required area for a percent-drop target scales with one-way length. 20 A at 10 ft can stay on 12 AWG; 20 A at 50 ft becomes 10 AWG on this page’s 120 V, 3% copper example.
How do I convert AWG to mm?
Use d(mm) = 0.127 × 92^((36 − AWG)/39). 12 AWG is 2.053 mm diameter and 3.309 mm². The converter and chart on this page use that formula for 4/0 through 40.
Is a larger AWG number a thicker wire?
No. A larger AWG number is thinner. 14 AWG is smaller than 12 AWG. 4/0 is the thickest size in the AWG converter here.
Can I use this calculator for 12V DC?
Yes. Choose DC and 12 V (or 24 V). Percent drop is much larger at low voltage, so 15 A over 10 ft at 3% recommends 8 AWG in the worked example.
Can I use this calculator for 240V?
Yes. Set 240 V (or 208, 277, or 480 V). A 20 A, 200 ft, 3% copper example recommends 8 AWG. Higher voltage reduces percent drop for the same ohms.
What is the difference between wire gauge and wire size?
Gauge usually means the AWG number. Size may mean AWG, mm², or the insulated cable’s outside diameter. This tool sizes the metal conductor.
Can I calculate wire size from watts?
Yes. Switch the load input to Watts. Single-phase or DC current is P / V at unity power factor; three-phase uses P / (√3 × V × PF). Power factor stays visible in Advanced options.
Is this calculator NEC compliant?
No. It is a free browser estimate using published AWG geometry, a voltage-drop area formula, and a shipped copper NM-B 60 °C ampacity table. It is not a code approval or a substitute for local requirements.
Accuracy and Safety Note
EverydayTools does not have a licensed electrician reviewer on this page. Results are browser-side estimates from the formulas and tables shown. Local electrical codes, insulation type, ambient temperature, conduit fill, termination ratings, and inspection requirements can require a different size. Do not use this output as the sole basis for a live installation.
Amps, watts, voltage, length, and other calculator inputs are processed only in your browser. EverydayTools does not upload those values. Last reviewed 2026-10-04.